Description
Sanhua YCVS Series: Features and Details
1. Core Function and Construction
-
Function: Ensures the correct and single direction of flow for the refrigerant, automatically closing to prevent backflow when pressure reverses.
-
Design Type: Piston Type Check Valve.
-
Mechanism: The piston moves within a cylinder, lifted by forward flow pressure and reseated by a spring (or reverse pressure) to seal.
-
-
Damping: Equipped with a damping spring.
-
Benefit: Allows the valve to be installed in various positions, including those with significant pressure pulses (like discharge lines), ensuring stable operation without flutter or noise.
-
-
Body Shapes: Available in two main body types for installation flexibility:
-
Straight-Way Valve (S-shape): For in-line installations.
-
L-Shape Valve (Angle shape): For installations requiring a 90 degree change in piping direction.
-
-
Installation: Flow direction corresponds to an arrow marked on the body.
2. Technical Specifications
-
Refrigerant Compatibility (Key Feature): Applicable for an extremely wide range of refrigerants, including:
-
Common HCFCs/HFCs (R22, R134a, R404A, R410A, R507A, etc.).
-
Low-GWP HFOs (R1234yf, R1234ze(E), etc.).
-
Flammable Refrigerants (A2L and A3), including R32 and R290 (Propane), making them future-proof.
-
Compatible with R744 (CO2) models (where specified).
-
-
Medium Temperature (TS): Wide operating range, typically -50^C to +150^C or +140^C (excellent high-temperature tolerance).
-
Max. Operating Pressure (PS): Very high rating, typically 4.6 MPa (46 bar) or 4.9 MPa (49 bar), depending on the model.
-
Pressure Drop: Designed for low pressure drops during operation, minimizing system efficiency loss.
3. Model Variations
-
YCVS (Standard): Models with a normal piston spring (Min. opening pressure difference (OPD) is usually low, e.g., $5\text{ kPa}$).
-
YCVSH (High Pressure): Special version equipped with a reinforced piston spring.
-
Application: Specifically applicable to compressor discharge pipes (hot gas lines) in single or multi-compressor systems where high backpressure and pressure pulses are common (Min. OPD is higher, e.g., 15 kPa or 30 kPa).
-
-
Connections: Available with ODF (solder) connections in a wide range of sizes (e.g., 1/4” up to 1-5/8”).