Sanhua P Series: Features and Details
1. Core Function and Construction
-
Function: Acts as a reservoir to catch and store liquid refrigerant that hasn’t evaporated, ensuring that only vapor enters the compressor suction port.
-
U-Tube Design: Features an internal U-shaped tube.3 Refrigerant vapor is drawn through the top of the U-tube, while liquid drops to the bottom of the vessel.
-
Oil Return Hole: Includes a precision-calibrated small hole at the bottom of the U-tube. This allows lubricating oil (and a metered amount of liquid refrigerant) to be drawn back into the compressor safely.
-
Materials: High-strength steel body with a powder-coated surface that can withstand over 500 hours of salt spray testing (anti-corrosion).
-
Internal Filter: Equipped with a screen to prevent debris from entering the compressor.
2. Technical Specifications
-
Refrigerant Compatibility: Applicable for all common HCFC and HFC refrigerants (R22, R134a, R404A, R407C, R410A, etc.).
-
Max. Working Pressure (PS): Typically rated up to 2.5 MPa (25bar).
-
Temperature Range:
-
Medium (TS): -30C to +120C.
-
Ambient: -35C to +55C.
-
-
Safety Feature: Often includes a fusible plug (e.g., rated at 430F / 221C) that melts in case of extreme fire/heat to prevent the vessel from exploding.
-
Connections: Solid copper ODF (solder) connections for easy installation.