Description
Detailed Physical and Chemical Properties
These specifications define the performance and stability of the oil in a refrigeration circuit.
| Property | Value | Unit | Notes |
| Kinematic Viscosity @ 40^C | 98 (Approx. 100) | mm2/s(cSt) | Confirms ISO VG 100 classification. |
| Kinematic Viscosity @ 100^C | 8.1 | mm2/s(cSt) | |
| Density @ 15^C | 870 | kg/m3 | |
| Flash Point | 196 (Range 170 to 196) | ^C | The temperature at which the oil vapor ignites. High value indicates safety. |
| Pour Point | -30 (Range -27 to -30) | ^C | Temperature below which oil becomes solid/loses flow characteristics. Low value is critical for low-temp refrigeration. |
| Thermal Stability | Excellent | – | Resistant to breakdown under high thermal loads (common in discharge gas). |
| Carbon Formation | Extremely Low | – | Minimizes sludge and carbon deposits, enhancing compressor life. |